Firestopping Requirements for Cable Trays and Wall/Slab Penetrations

Author : Adrian September 26, 2025

1. Cable Tray Wall Penetration Firestopping

1. Electrical cable tray wall penetration firestopping

  1. Scope: Firestopping for busway, cable trays, cables, and trunking passing through walls in enclosed electrical installations.

 

  1. Photograph

Core Procedures

  1. Where cables pass through shafts, walls, slabs, or enter electrical panels or cabinets, openings shall be tightly sealed with firestopping materials in accordance with design requirements.
  2. Process flow: reserved openings → busway installation → distribution box positioning and installation → conduit installation → cable routing → grounding → waterproof step → firestopping.
  3. Working conditions: floor and wall finishes in the electrical shaft completed, and shaft doors installed.
  4. Sealing shall be tight and reliable, without visible cracks or voids. For large openings, install a fire-resistant backing plate before sealing.
  5. Installation requirements:
    1. Layout and positioning must be reasonable to facilitate installation and maintenance.
    2. Choose appropriate fire protection materials, such as fire-rated board, firestop packs, firestop mastic, or fire-resistant mineral wool.
    3. Firestop packs should be placed in an orderly sequence. The gap area between firestop packs and cables should not exceed 1 cm2, and the packing thickness should be not less than 24 cm.
    4. All gaps inside and around metal trunking must be sealed tightly and be complete both internally and externally.
  6. Cover plates should be square, of consistent suitable dimensions, painted evenly, and used to close the opening.

2. Firestopping at Slab Penetrations for Electrical Shafts

Scope: Firestopping for busway, cable trays, cables, and trunking where they pass through slabs in electrical shafts.

Photograph

Key Process Points

  1. Where cables pass through shafts, walls, slabs, or enter electrical panels or cabinets, openings shall be tightly sealed with firestopping materials in accordance with design requirements.
  2. An electrical shaft shall have a threshold. Cable trays and busways at floor level or at slab penetrations shall have a waterstop no less than 50 mm in height.
  3. At slab penetrations, provide 20–30 mm of firestopping and install a fire-support plate at the top.
  4. Sealing shall be tight and reliable, without visible cracks or voids. For large openings, install a fire-resistant backing plate before sealing.
  5. Installation requirements:
    1. Layout and positioning must be reasonable to facilitate installation and maintenance.
    2. Choose appropriate fire protection materials, such as fire-rated board, firestop packs, firestop mastic, or fire-resistant mineral wool.
    3. Firestop packs should be placed in an orderly sequence. The gap area between firestop packs and cables should not exceed 1 cm2, and the packing thickness should be not less than 24 cm.
    4. All gaps inside and around metal trunking must be sealed tightly and be complete both internally and externally.
  6. Cover plates should be square, of consistent suitable dimensions, painted evenly, and used to close the opening.
Recommended Reading
Optimal Location for Low-Voltage Power Factor Panels

Optimal Location for Low-Voltage Power Factor Panels

September 26, 2025

Comparison of PFC cabinet installation upstream vs downstream in a distribution room, assessing through-busbar capacity, ambient temperature impact, and correction effectiveness.

Article
Two Automation Modes for Central Control Stations

Two Automation Modes for Central Control Stations

September 26, 2025

Technical overview of central control station for unmanned substations: compares hierarchical management mode and centralized control mode, with SCADA/dispatch integration.

Article
Responding to High-Power Outages in Outdoor Construction

Responding to High-Power Outages in Outdoor Construction

September 25, 2025

Review of portable power options and large-capacity mobile energy stations for prolonged, high-power outages: specifications, output, cycle life, safety, and deployment.

Article
Purpose and Requirements of Automatic Reclosers

Purpose and Requirements of Automatic Reclosers

September 25, 2025

Overview of automatic reclosers, advantages, risks, and implementation principles for single-phase adaptive reclosing and comprehensive automatic reclosing in power systems.

Article
Are AC Terminals the Same as AC Cables? Inverter Installation Steps

Are AC Terminals the Same as AC Cables? Inverter Installation Steps

September 25, 2025

Technical guide to inverter AC cable selection for residential and commercial installations, comparing copper and aluminum conductors and outlining wiring and commissioning steps.

Article
Substation Secondary Systems: Common Equipment

Substation Secondary Systems: Common Equipment

September 25, 2025

Technical overview of terminal block design and front panel layout principles for secondary equipment, covering terminal types, arrangement, and panel diagrams.

Article